 a
FEATURES Low Cost Operates with Type J (AD596) or Type K (AD597) Thermocouples Built-In Ice Point Compensation Temperature Proportional Operation - 10 mV/ C Temperature Setpoint Operation - ON/OFF Programmable Switching Hysteresis High Impedance Differential Input
Thermocouple Conditioner and Setpoint Controller AD596*/AD597*
FUNCTIONAL BLOCK DIAGRAM TO-100
-ALM -IN +ALM
+IN ICE POINT COMP
- G + - G + + +A
V+
GENERAL DESCRIPTION
The AD596/AD597 is a monolithic temperature setpoint controller that has been optimized for use at elevated temperatures such as those found in oven control applications. The device cold junction compensates and amplifies a type J or K thermocouple input to derive an internal signal proportional to temperature. The internal signal is then compared with an externally applied setpoint voltage to yield a low impedance switched output voltage. Dead-Band or switching hysteresis can be programmed using a single external resistor. Alternately, the AD596/AD597 can be configured to provide a voltage output (10 mV/C) directly from a type J or K thermocouple signal. It can also be used as a standalone voltage output temperature sensor. The AD596/AD597 can be powered with a single supply from +5 V to +30 V, or dual supplies up to a total span of 36 V. Typical quiescent supply current is 160 A, which minimizes self-heating errors. The AD596/AD597 H package option includes a thermocouple failure alarm that indicates an open thermocouple lead when operated in the temperature proportional measurement mode. The alarm output has a flexible format which can be used to drive relays, LEDs or TTL logic. The device is packaged in a reliability qualified, cost effective 10-pin metal can or SOIC and is trimmed to operate over an ambient temperature range from +25C to +100C. Operation over an extended ambient temperature range is possible with slightly reduced accuracy. The AD596 will amplify thermocouple signals covering the entire -200C to +760C temperature range recommended for type J thermocouples while the AD597 can accommodate -200C to +1250C type K inputs. The AD596/AD597 has a calibration accuracy of 4C at an ambient temperature of 60C and an ambient temperature stability specification of 0.05C/C from +25C to +100C. If higher accuracy, or a lower ambient operating temperature is required, either the AD594 (J thermocouple) or AD595 (K thermocouple) should be considered.
*Protected by U.S. Patent No. 4,029,974.
HYS
AD596/ AD597
VOUT
GND V-
FB
SOIC
AD597
+IN 1 + G HYS 2 + G - +A 7 V+ - 8 -IN
GND 3
+
6 VOUT
V- 4
ICE POINT COMP TOP VIEW (Not to Scale)
5 FB
PRODUCT HIGHLIGHTS
1. The AD596/AD597 provides cold junction compensation and a high gain amplifier which can be used as a setpoint comparator. 2. The input stage of the AD596/AD597 is a high quality instrumentation amplifier that allows the thermocouple to float over most of the supply voltage range. 3. Linearization not required for thermocouple temperatures close to 175C (+100C to +540C for AD596). 4. Cold junction compensation is optimized for ambient temperatures ranging from +25C to +100C. 5. In the stand-alone mode, the AD596/AD597 produces an output voltage that indicates its own temperature.
REV. B
Information furnished by Analog Devices is believed to be accurate and reliable. However, no responsibility is assumed by Analog Devices for its use, nor for any infringements of patents or other rights of third parties which may result from its use. No license is granted by implication or otherwise under any patent or patent rights of Analog Devices. One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A. Tel: 781/329-4700 World Wide Web Site: http://www.analog.com Fax: 781/326-8703 (c) Analog Devices, Inc., 1998
AD596/AD597-SPECIFICATIONS unless otherwise noted)
Model Min ABSOLUTE MAXIMUM RATINGS +VS to -VS Common-Mode Input Voltage Differential Input Voltage Alarm Voltages +ALM -ALM Operating Temperature Range Output Short Circuit to Common TEMPERATURE MEASUREMENT (Specified Temperature Range +25C to +100C) Calibration Error1 Stability vs. Temperature2 Gain Error Nominal Transfer Function AMPLIFIER CHARACTERISTICS Closed Loop Gain3 Input Offset Voltage Input Bias Current Differential Input Range Common-Mode Range Common-Mode Sensitivity-RTO Power Supply Sensitivity-RTO Output Voltage Range Dual Supplies Single Supply Usable Output Current4 3 dB Bandwidth ALARM CHARACTERISTICS VCE(SAT) at 2 mA Leakage Current Operating Voltage at - ALM Short Circuit Current POWER REQUIREMENTS Operating Quiescent Current +VS -VS
NOTES
1
(@ +60 C and VS = 10 V, Type J (AD596), Type K (AD597) Thermocouple,
AD597AH Typ AD597AR Typ
AD596AH Typ Max 36 +VS +VS (-VS +36) +VS +125
Min
Max 36 +VS +VS (-VS +36) +VS +125
Min
Max 36 +VS +VS (-VS +36) +VS +125
Units Volts Volts Volts Volts Volts C
(-VS - 0.15) -VS -VS -VS -55 Indefinite
(-VS - 0.15) -VS -VS -VS -55 Indefinite
(-VS - 0.15) -VS -VS -VS -40 Indefinite
-4 -1.5
0.02 10
+4 0.05 +1.5
-4 -1.5
0.02 10 245.5 C x 41.27 - 37 0.1
+4 0.05 +1.5
-4 -1.5
0.02 10 245.5 C x 41.27 - 37 0.1
+4 0.05 +1.5
C C/C % mV/C V/V V A mV Volts mV/V mV/V Volts Volts mA kHz Volts A Volts mA
180.6 C x 53.21 + 235 0.1 -10 +50 (-VS - 0.15) (+V S - 4) 10 1 10 (-VS + 2.5) 0 5 15 0.3 1 (+VS - 4) 20 (+VS to -VS) 30 160 100 300 200 (+VS - 2) (+VS - 2)
-10 (+VS - 0.15) 1 (-VS + 2.5) 0 5 15 0.3
+50 (+VS - 4) 10 10 (+VS - 2) (+VS - 2)
-10 (-VS - 0.15) 1 (-VS + 2.5) 0 5 15
+50 (+V S - 4) 10 10 (+VS - 2) (+VS - 2)
5
Alarm Function Not Pinned Out 1 (+VS - 4) 20 (+VS to -VS) 30 160 100 300 200 (+VS to -VS) 30 160 100 300 200
Volts A A
This is a measure of the deviation from ideal with a measuring thermocouple junction of 175C and a chip temperature of 60C. The ideal transfer function is given by: AD596: VOUT = 180.57 x (Vm - Va + (ambient in C) x 53.21 V/C + 235 V) AD597: VOUT = 245.46 x (Vm - Va + (ambient in C) x 41.27 V/C - 37 V) where Vm , and Va represent the measuring and ambient temperatures and are taken from the appropriate J or K thermocouple table. The ideal transfer function minimizes the error over the ambient temperature range of 25C to 100C with a thermocouple temperature of approximately 175C. 2 Defined as the slope of the line connecting the AD596/AD597 CJC errors measured at 25C and 100C ambient temperature. 3 Pin 6 shorted to Pin 7. 4 Current Sink Capability in single supply configuration is limited to current drawn to ground through a 50 k resistor at output voltages below 2.5 V. 5 Alarm function available on H package option only. Specifications subject to change without notice. Specifications shown in boldface are tested on all production units at final electrical test. Results from those tests are used to calculate outgoing quality levels. All min and max specifications are guaranteed, although only those shown in boldface are tested on all production units.
ORDERING GUIDE
Model AD596AH AD597AH AD597AR*
Package Description TO-100 TO-100 Plastic SOIC
Package Options H-10A H-10A SO-8
*Consult factory for availability.
-2-
REV. B
AD596/AD597
Table I. Output Voltage vs. Thermocouple Temperature (Ambient +60 C, VS = -5 V, +15 V)
Thermocouple Temperature C -200 -180 -160 -140 -120 -100 -80 -60 -40 -20 -10 0 10 20 25 30 40 50 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 Type J Voltage mV -7.890 -7.402 -6.821 -6.159 -5.426 -4.632 -3.785 -2.892 -1.960 -.995 -.501 0 .507 1.019 1.277 1.536 2.058 2.585 3.115 4.186 5.268 6.359 7.457 8.560 9.667 10.777 11.887 12.998 14.108 15.217 16.325 17.432 18.537 19.640 20.743 21.846 22.949 24.054 25.161 26.272 AD596 Output mV -1370 -1282 -1177 -1058 -925 -782 -629 -468 -299 -125 -36 54 146 238 285 332 426 521 617 810 1006 1203 1401 1600 1800 2000 2201 2401 2602 2802 3002 3202 3402 3601 3800 3999 4198 4398 4598 4798 Type K Voltage mV -5.891 -5.550 -5.141 -4.669 -4.138 -3.553 -2.920 -2.243 -1.527 -.777 -.392 0 .397 .798 1.000 1.203 1.611 2.022 2.436 3.266 4.095 4.919 5.733 6.539 7.338 8.137 8.938 9.745 10.560 11.381 12.207 13.039 13.874 14.712 15.552 16.395 17.241 18.088 18.938 19.788 AD597 Output mV -1446 -1362 -1262 -1146 -1016 -872 -717 -551 -375 -191 -96 0 97 196 245 295 395 496 598 802 1005 1207 1407 1605 1801 1997 2194 2392 2592 2794 2996 3201 3406 3611 3817 4024 4232 4440 4649 4857 Thermocouple Temperature C 500 520 540 560 580 600 620 640 660 680 700 720 740 750 760 780 800 820 840 860 880 900 920 940 960 980 1000 1020 1040 1060 1080 1100 1120 1140 1160 1180 1200 1220 1240 1250 Type J Voltage mV 27.388 28.511 29.642 30.782 31.933 33.096 34.273 35.464 36.671 37.893 39.130 40.382 41.647 42.283 - - - - - - - - - - - - - - - - - - - - - - - - - - AD596 Output mV 5000 5203 5407 5613 5821 6031 6243 6458 6676 6897 7120 7346 7575 7689 - - - - - - - - - - - - - - - - - - - - - - - - - - Type K Voltage mV 20.640 21.493 22.346 23.198 24.050 24.902 25.751 26.599 27.445 28.288 29.128 29.965 30.799 31.214 31.629 32.455 33.277 34.095 34.909 35.718 36.524 37.325 38.122 38.915 39.703 40.488 41.269 42.045 42.817 43.585 44.439 45.108 45.863 46.612 47.356 48.095 48.828 49.555 50.276 50.633 AD597 Output mV 5066 5276 5485 5694 5903 6112 6321 6529 6737 6944 7150 7355 7560 7662 7764 7966 8168 8369 8569 8767 8965 9162 9357 9552 9745 9938 10130 10320 10510 10698 10908 11072 11258 11441 11624 11805 11985 12164 12341 12428
REV. B
-3-
AD596/AD597
TEMPERATURE PROPORTIONAL OUTPUT MODE
The AD596/AD597 can be used to generate a temperature proportional output of 10 mV/C when operated with J and K type thermocouples as shown in Figure 1. Thermocouples produce low level output voltages which are a function of both the temperature being measured and the reference or cold junction temperature. The AD596/AD597 compensates for the cold junction temperature and amplifies the thermocouple signal to produce a high level 10 mV/C voltage output which is a function only of the temperature being measured. The temperature stability of the part indicates the sensitivity of the output voltage to changes in ambient or device temperatures. This is typically 0.02C/C over the +25C to +100C recommended ambient temperature range. The parts will operate over the extended ambient temperature ranges from -55C to +125C, but thermocouple nonlinearity at the reference junction will degrade the temperature stability over this extended range. Table I is a list of ideal AD596/AD597 output voltages as a function of Celsius temperature for type J and K ANSI standard thermocouples with package and reference junction at 60C. As is normally the case, these outputs are subject to calibration and temperature sensitivity errors. These tables are derived using the ideal transfer functions: AD596 output = (Type J voltage + 301.5 V) x 180.57 AD597 output = (Type K voltage) x 245.46
CONSTANTAN (ALUMEL) +5V TO +30V
Excluding calibration errors, the above transfer function is accurate to within 1C from +80C to +550C for the AD596 and -20C to +350C for the AD597. The different temperature ranges are due to the differences in J and K type thermocouple curves. European DIN FE-CuNi thermocouple vary slightly from ANSI type J thermocouples. Table I does not apply when these types of thermocouples are used. The transfer functions given previously and a thermocouple table should be used instead. Figure 1 also shows an optional trimming network which can be used to change the device's offset voltage. Injecting or sinking 200 nA from Pin 3 will offset the output approximately 10 mV (1C). The AD596/AD597 can operate from a single supply from 5 V to 36 V or from split supplies totalling 36 V or less as shown. Since the output can only swing to within 2 V of the positive supply, the usable measurement temperature range will be restricted when positive supplies less than 15 V for the AD597 and 10 V for the AD596 are used. If the AD596/AD597 is to be used to indicate negative Celsius temperatures, then a negative supply is required. Common-mode voltages on the thermocouple inputs must remain within the common-mode voltage range of the AD596/ AD597, with a return path provided for the bias currents. If the thermocouple is not remotely grounded, then the dotted line connection shown in Figure 1 must be made to one of the thermocouple inputs. If there is no return path for the bias currents, the input stage will saturate, causing erroneous output voltages. In this configuration, the AD596/AD597 H package option has circuitry which detects the presence of an open thermocouple. If the thermocouple loop becomes open, one or both of the inputs to the device will be deprived of bias current causing the output to saturate. It is this saturation which is detected internally and used to activate the alarm circuitry. The output of this feature has a flexible format which can be used to source or sink up to 20 mA of current. The collector (+ALM) should not be allowed to become more positive than (-VS + 36 V), however, it may be permitted to be more positive than +VS. The emitter voltage (-ALM) should be constrained such that it does not become more positive than 4 V below +VS. If the alarm feature is not used, this pin should be connected to Pins 4 or 5 as shown in Figure 1. The alarm function is unavailable on the AR package option.
IRON (CHROMEL) OPTIONAL OFFSET 10k ADJUST 100k 100k
+15V 1M
AD596/ AD597*
0.01 F VOUT SPAN OF +5V TO +30V
-15V
0.01 F
0 TO -25V *H PACKAGE PINOUT SHOWN
Figure 1. Temperature Proportional Output Connection
The offsets and gains of these devices have been laser trimmed to closely approximate thermocouple characteristics over measurement temperature ranges centered around 175C with the AD596/AD597 at an ambient temperature between 25C and 100C. This eliminates the need for additional gain or offset adjustments to make the output voltage read: VOUT = 10 mV/C x (thermocouple temperature in C) (within specified tolerances).
-4-
REV. B
AD596/AD597
SETPOINT CONTROL MODE
The AD596/AD597 can be connected as a setpoint controller as shown in Figure 2. The thermocouple voltage is cold junction compensated, amplified, and compared to an external setpoint voltage. The relationship between setpoint voltage and temperature is given in Table I. If the temperature to be controlled is within the operating range (-55C to +125C) of the device, it can monitor its own temperature by shorting the inputs to ground. The setpoint voltage with the thermocouple inputs grounded is given by the expressions: AD596 Setpoint Voltage = C x 9.6 mV/C + 42 mV AD597 Setpoint Voltage = C x 10.1 mV/C - 9.1 mV The input impedance of the setpoint pin of the AD596/AD597 is approximately 50 k. The temperature coefficient of this resistance is 15 ppm/C. Therefore, the 100 ppm/C 5 k pot shown in Figure 2 will only introduce an additional 1C degradation of temperature stability over the +25C to +100C ambient temperature range.
TEMPERATURE CONTROLLED CONSTANTAN (ALUMEL) REGION
- G + ICE POINT COMP - G + + +A
+VS
0.01 F
AD596/ AD597*
VOUT 9.6mV/ C
*H PACKAGE PINOUT SHOWN 0.01 F -VS
Figure 3. Stand-Alone Temperature Transducer Temperature Proportional Output Connection
IRON (CHROMEL)
AD596/ AD597*
TEMPERATURE COMPARATOR 0.01 F OUTPUT +V VREF SETPOINT VOLTAGE SETPOINT VOLTAGE 5k 100ppm/ C
Simply omit the thermocouple and connect the inputs (Pins 1 and 2) to common. The output will now reflect the compensation voltage and hence will indicate the AD596/AD597 temperature. In this three terminal, voltage output, temperature sensing mode, the AD596/AD597 will operate over the full extended -55C to +125C temperature range. The output scaling will be 9.6 mV per C with the AD596 and 10.1 mV per C with the AD597. Additionally there will be a 42 mV offset with the AD596 causing it to read slightly high when used in this mode.
THERMOCOUPLE CONNECTIONS
R HYSTERESIS (OPTIONAL)
HEATER DRIVER *H PACKAGE PINOUT SHOWN
Figure 2. Setpoint Control Mode
Switching hysteresis is often used in setpoint systems of this type to provide noise immunity and increase system reliability. By reducing the frequency of on-off cycling, mechanical component wear is reduced leading to enhanced system reliability. This can easily be implemented with a single external resistor between Pins 7 and 3 of the AD596/AD597. Each 200 nA of current injected into Pin 3 when the output switches will cause about 1C of hysteresis; that is: RHYST () = V OUT 1 x 200 nA CHYST
The connection of the thermocouple wire and the normal wire or printed circuit board traces going to the AD596/AD597 forms an effective reference junction as shown in Figure 4. This junction must be kept at the same temperature as the AD596/ AD597 for the internal cold junction compensation to work properly. Unless the AD596/AD597 is in a thermally stable enclosure, the thermocouple leads should be brought in directly to Pins 1 and 2.
REFERENCE JUNCTION LIMITING RESISTOR TO LED 0.01 F +VS
CONSTANTAN (ALUMEL) IRON (CHROMEL) NOTE: A BIAS RETURN PATH FROM PINS 1 AND 2 OF LESS THAN 1k IMPEDANCE MUST BE PROVIDED.
AD596/ AD597*
VOUT
In the setpoint configuration, the AD596/AD597 output is saturated at all times, so the alarm transistor will be ON regardless of whether there is an open circuit or not. However, -ALM must be tied to a voltage below (+VS - 4 V) for proper operation of the rest of the circuit.
STAND-ALONE TEMPERATURE TRANSDUCER
GND
0.01 F *H PACKAGE PINOUT SHOWN
-VS
The AD596/AD597 may be configured as a stand-alone Celsius thermometer as shown in Figure 3.
Figure 4. PCB Connections
To ensure secure bonding, the thermocouple wire should be cleaned to remove oxidization prior to soldering. Noncorrosive resin flux is effective with iron, constantan, chromel, and alumel, and the following solders: 95% tin-5% silver, or 90% tin-10% lead.
REV. B
-5-
AD596/AD597
SINGLE AND DUAL SUPPLY CONNECTIONS
In the single supply configuration as used in the setpoint controller of Figure 2, any convenient voltage from +5 V to +36 V may be used, with self-heating errors being minimized at lower supply levels. In this configuration, the -VS connection at Pin 5 is tied to ground. Temperatures below zero can be accommodated in the single supply setpoint mode, but not in the single supply temperature measuring mode (Figure 1 reconnected for single supply). Temperatures below zero can only be indicated by a negative output voltage, which is impossible in the single supply mode. Common-mode voltages on the thermocouple inputs must remain below the positive supply, and not more than 0.15 V more negative than the minus supply. In addition, a return path for the input bias currents must be provided. If the thermocouple is not remotely grounded, then the dotted line connections in Figures 1 and 2 are mandatory. The AD596/AD597 is specified for a maximum error of 4C at an ambient temperature of 60C and a measuring junction temperature at 175C. The ambient temperature stability is specified to be a maximum of 0.05C/C. In other words, for every degree change in the ambient temperature, the output will change no more than 0.05 degrees. So, at 25C the maximum deviation from the temperature-voltage characteristic of Table I is 5.75C, and at 100C it is 6C maximum (see Figure 5). If the offset error of 4C is removed with a single offset adjustment, these errors will be reduced to 1.75C and 2C max. The optional trim circuit shown in Figure 1 demonstrates how the ambient offset error can be adjusted to zero.
+2.0 C +1.75 C
temperature differences will result in a direct error at the output. In the temperature proportional mode, the alarm feature will only activate in the event of an open thermocouple or system transient which causes the device output to saturate. Self-Heating errors will not effect the operation of the alarm but two cases do need to be considered. First, after a fault is corrected and the alarm is reset, the AD596/AD597 must be allowed to cool before readings can again be accurate. This can take 5 minutes or more depending upon the thermal environment seen by the device. Second, the junction temperature of the part should not be allowed to exceed 150C. If the alarm circuit of the AD596/AD597 is made to source or sink 20 mA with 30 V across it, the junction temperature will be 90C above ambient causing the die temperature to exceed 150C when ambient is above 60C. In this case, either the load must be reduced, or a heat sink used to lower the thermal resistance. TEMPERATURE READOUT AND CONTROL Figure 6 shows a complete temperature indication and control system based on the AD596/AD597. Here the AD596/AD597 is being used as a closed-loop thermocouple signal conditioner and an external op amp is used to implement setpoint. This has two important advantages. It provides a high level (10 mV/C) output for the A/D panel meter and also preserves the alarm function for open thermocouples. The A/D panel meter can easily be offset and scaled as shown to read directly in degrees Fahrenheit. If a two temperature calibration scheme is used, the dominant residual errors will arise from two sources; the ambient temperature rejection (typically 2C over a 25C to 100C range) and thermocouple nonlinearity typical +1C from 80C to 550C for type J and +1C from -20C to 350C for type K. An external voltage reference is used both to increase the stability of the A/D converter and supply a stable reference for the setpoint voltage.
STABILITY OVER TEMPERATURE
MAXIMUM
+0.8 C 0 -0.8 C
MAXIMUM TYPICAL
-1.75 C -2.0 C 25 C 60 C 100 C
Figure 5. Drift Error vs. Temperature
THERMAL ENVIRONMENTAL EFFECTS
The inherent low power dissipation of the AD596/AD597 keeps self-heating errors to a minimum. However, device output is capable of delivering 5 mA to an external load and the alarm circuitry can supply up to 20 mA. Since the typical junction to ambient thermal resistance in free air is 150C/W, significant temperature difference between the package pins (where the reference junction is located) and the chip (where the cold junction temperature is measured and then compensated) can exist when the device is operated in a high dissipation mode. These
A traditional requirement for the design of setpoint control thermocouple systems has been to configure the system such that the appropriate action is taken in the event of an open thermocouple. The open thermocouple alarm pin with its flexible current-limited output format supports this function when the part operates in the temperature proportional mode. In addition, if the thermocouple is not remotely grounded, it is possible to program the device for either a positive or negative full-scale output in the event of an open thermocouple. This is done by connecting the bias return resistor directly to Pin 1 if a high output voltage is desired to indicate a fault condition. Alternately, if the bias return is provided on the thermocouple lead connected to Pin 2, an open circuit will result in an output low reading. Figure 6 shows the ground return connected to Pin 1 so that if the thermocouple fails, the heater will remain off. At the same time, the alarm circuit lights the LED signalling the need to service the thermocouple. Grounding Pin 2 would lead to low output voltage saturation, and in this circuit would result in a potentially dangerous thermal runaway under fault conditions.
-6-
REV. B
AD596/AD597
+V READOUT F
TEMPERATURE
CONSTANTAN (ALUMEL)
470 - + +V 45.2k 10k IN LO 1.27M +V *H PACKAGE PINOUT SHOWN 5V AD584 10k REF LO 40.2k REF HI ICL7136 IN HI LCD DISPLAY
IRON (CHROMEL) HEATER
AD596/ AD597*
SET-POINT ADJUST 5k
-
10k OP07
1k
+
10M 120V AC
Figure 6. Temperature Measurement and Control
REV. B
-7-
AD596/AD597
OUTLINE DIMENSIONS
Dimensions shown in inches and (mm).
10-Pin Metal Can (TO-100)
C831b-5-2/98
8 4 9 3 2 0.040 (1.02) MAX 0.045 (1.14) 0.010 (0.25) 0.019 (0.48) 0.016 (0.41) 0.230 (5.84) BSC 0.021 (0.53) 0.016 (0.41) 10 1 0.034 (0.86) 0.027 (0.69) 0.045 (1.14) 0.027 (0.69) REFERENCE PLANE 0.185 (4.70) 0.165 (4.19) 0.750 (19.05) 0.500 (12.70) 0.250 (6.35) MIN 0.050 (1.27) MAX
0.160 (4.06) 0.110 (2.79) 6
0.370 (9.40) 0.335 (8.51) 0.335 (8.51) 0.305 (7.75)
5 0.115 (2.92) BSC
7
36 BSC
BASE & SEATING PLANE
8-Lead Small Outline (SOIC) (SO-8)
0.1968 (5.00) 0.1890 (4.80)
8 1 5 4
0.1574 (4.00) 0.1497 (3.80)
0.2440 (6.20) 0.2284 (5.80)
PIN 1 0.0098 (0.25) 0.0040 (0.10)
0.0688 (1.75) 0.0532 (1.35)
0.0196 (0.50) x 45 0.0099 (0.25)
0.0500 0.0192 (0.49) SEATING (1.27) 0.0098 (0.25) PLANE BSC 0.0138 (0.35) 0.0075 (0.19)
8 0 0.0500 (1.27) 0.0160 (0.41)
-8-
REV. B
PRINTED IN U.S.A.
This datasheet has been download from: www..com Datasheets for electronics components.


▲Up To Search▲   

 
Price & Availability of AD596ACHIPS

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X